Sprinkler introduction-What’s Fire Sprinkler
Dec 27, 2023
What's Fire Sprinkler
It is a nozzle that in the case of heat, according to the predetermined temperature range to start their own, or start by the control device according to the fire signal, then sprinkled water according to the designed shape and flow.

Deflector:At the top of the nozzle, make sure the water can be sprinkled into a predetermined sprinkler shape.
Frame:Refers to the support arm of the nozzle and its connecting part.

Heat sensitive components
The component which capable of operating the fire sprinkler at a predetermined temperature.
Nominal Diameter
The nominal size of the sprinkler water outlet which according to the size of the flow.
Release mechanism
The mechanism consists of heat sensitive components, seals and other related parts. It is the part, when the sprinkler starts, can automatically out of the sprinkler body.
Static operating temperature
In an experimental setting, heating according to the provisions conditions, the temperature which the thermal sensitive components action after heating.
|
Glass Bulb Fire Sprinkler |
Fusible Alloy Fire Sprinkler |
||
|
Temperature Rating |
Colour Standard |
Temperature Rating |
Colour Standard |
|
57 |
Orange |
57~77 |
Self-colour |
|
68 |
Red |
80~107 |
White |
|
79 |
Yellow |
121~149 |
Blue |
|
93 |
Green |
163~191 |
Red |
|
100 |
Gray |
204~246 |
Green |
|
121 |
Azure |
260~302 |
Orange |
|
141 |
Blue |
|
|
*For 68℃, the requirement is above 60% should burst between 68℃±3℃, above 80% should burst before 74℃
Nominal Action Temperature
Indicates the nominal operating temperature of the closed sprinkler in different temperature ranges under different environmental conditions.
Deposition
After the sprinkler is operated, the parts of the release mechanism or the fragments of the thermal element remain in the nozzle frame or the deflector and so on, which will obviously affect the nozzle to sprinkled according to the designed shape for more than 1min.
State Bureau of Technical Supervision 1993-01-20 approved 1993-09-01 implementation of GB 5135-93