Dry Pipe Sprinkler Fire Alarm Valve
A dry pipe fire alarm valve is a latching, differential-style control valve that holds back water in a dry pipe sprinkler system until a fire activates a sprinkler head.
The system's pipes are filled with compressed air or nitrogen, not water, which prevents freezing in unheated areas.
When a sprinkler opens, the air pressure drops, allowing the water pressure to overcome the differential and open the valve, flooding the system and extinguishing the fire.
Fujian Haijing Fire Fighting Equipment Co., Ltd. is one of the leading manufacturers and suppliers of dry pipe sprinkler fire alarm valve in China, also supports customized service. Please feel free to wholesale cheap dry pipe sprinkler fire alarm valve from our factory.
Specifications of Dry Pipe Sprinkler Fire Alarm Valve
|
Alarm Check Valve (Dry Type) Basic Technical Info |
|||
|
Model |
ZSFC80 |
ZSFC150 |
ZSFC200 |
|
Inside nominal diameter(mm) |
80 |
150 |
200 |
|
Rated working pressure (MPa) |
1.2MPa |
||
|
Sealed test (MPa) |
2.4MPa |
||
|
Strength test (MPa) |
4.8MPa |
||
|
Alarm flow (L/min) |
"15 Q<170 @1.6MPa" |
||
|
Retard alarm time(s) |
5~90 |
||
|
Alarm Bell Start Pressure(MPa) |
≤0.035 |
||
|
Friction Resistance(MPa) |
≤0.02 |
||
|
"Height of alarm valve(mm) |
375 |
450 |
576 |
|
"Outside diameter of flange (mm)" |
220 |
285 |
340 |
|
"Outside diameter of flange screw hole (mm)" |
180 |
240 |
295 |
|
"Diameter of screw hole (mm) |
8 |
||
|
Quantity of screw hole |
18 |
22 |
22 |




When a Dry Pipe Sprinkler Fire Alarm Valve trips the accelerator?
The Accelerator automatically adjusts to both small and slow changes in sys- tem pressure but trips when there is a rapid and steady drop in pressure (such as will occur when a sprinkler operates). Upon tripping, the Accelera- tor transmits system air pressure to the intermediate chamber of the dry pipe valve.
Company Information



FAQ
Q: How much air pressure must be maintained?
A: Normal system air is 40 psi (2.8 bar) with a 5:1 differential to water supply; a low-air supervisory switch signals at 30 psi (≈ 10 psi drop) to give a pre-trouble warning .
Q: How is the Dry Pipe Sprinkler Fire Alarm Valve reset after activation?
A: Close the supply control valve, drain the system, restore air pressure to above the trip point, then open the external-reset knob (or remove the face-plate on older models) to latch the clapper closed; finally reopen the water supply